| Water-heating stationary horizontal fire-tube boiler made of steel 09G2S, with a furnace shell thickness of 14 mm, a body shell thickness of 10 mm, with mineral wool insulation and stainless steel casing 0.5 mm thick |
| Ruff for cleaning fire tubes |
| Passport and operating manual |
| Set of attachments for boiler KVA-3.0 |
| Gas burner Baltur TBG 360MS |
| Gas fittings MM40.065 A120C-R2 |
| Axial compensator BTGA DN65 |
| Leak control unit VPS504.S02 (optional) |
| Diesel burner Baltur TBL-360 P |
| Fitting kit for diesel burner |
| Nozzle Danfoss 31.50x60° B |
| Burner combined gas-diesel |
| Burner for fuel oil (spent fuel) |
| Sandwich chimney |
| The block container with viewing windows |
| Diesel fuel tank BDT-0.6 |
| Tank for diesel fuel BDT-1 |
| Diesel fuel tank BDT-5 |
| Diesel fuel tank BDT-7 |
| Tank for diesel fuel BDT-10 |
| Tank for diesel fuel BDT-25 |
Heating hot water boiler HEAT KVA-3.0 Gn/LV It is used as an independent thermal unit for heating coolants in open and closed circuits of heating systems, and as part of thermal systems with a closed circuit when organizing heating and hot water supply (DHW) of civil and industrial premises with a nominal pressure in the primary circuit up to 0.6 MPa and temperatures up to 105 ° C. Coolants can be water, solutions based on propylene and ethylene glycol (antifreeze) with a concentration of up to 50%.
Boilers can be equipped burnersoperating on various types of fuel (diesel, gas, fuel oil, heating oil)
boiler HEAT KVA-3.0 Gn/LV supplied on a frame in climate version UHL4.
KVA hot water boilers have a TR TS 016 certificate, a TR TS declaration 001, 010, 020 and voluntary certification according to the GOST R system.
[parent] => 45 [count] => 6 [filter] => raw )
The price for the heating center does not include attachments and burner
- To provide hot water and heating
- Time to enter operating mode – from 20 minutes
- Automatic control, high efficiency – 92%
- Convenient service
- Low fuel consumption
Technical Features
- Thermal power, MW 3
- Design pressure, MPa 0,6
- Test pressure, MPa 0,9
- Maximum coolant temperature, °C 105
- Internal heating area, m2 85
- Boiler internal volume, m3 2,7
- The volume of the ball, m3 1,828
- Connecting diameter of supply and return, DN, mm 200
- Connecting size of a drain branch pipe, DN, mm 25
- Thermal power of the burner, MW 3260
- Reject hopper capacity (at a density of 1.8 t/m³), m³ (t) 2,58
- Diesel fuel consumption, kg/hour 273
- Diesel fuel consumption, l/h 329
- Methane consumption, nm3/hour 348
- Time to exit to mode, min 20-40
- Boiler weight (without attachments), kg. 6700
- Length, mm 4450
- Width, mm 1900
- Height, mm 2357
- Climatic version UHL4
Quality
certificates
Products
in stock
Individual configuration
with prices for each item
Mobile
commissioning
available
Worldwide
delivery
in trucks or containers
Geography of supplies 2011-2026
Own production, in-stock products and
professional team allow us guarantee
most competitive prices, shortest
possible delivery time and high-quality goods
Call, hotline in the Republic of Belarus
Our managers will answer all your questions from Monday till Friday:
from 06:00 a.m. to 05:00 p.m. (GMT+3, Moscow time)
Address: Republic of Belarus, 220073, Minsk, st. Olshevskogo, 20, office. 38a
e-mail: sales@zzbo.ru


Denis Zhilyakov
Director of the branch in the Republic of Belarus
Phone: +7 (963) 914-75-75
e-mail: sales@zzbo.ru
Place your order
We will send you the price,
conditions and terms of delivery
Response within 1 hour
You will get the offer with
individual delivery and payment conditions